en | Installation
The temperature-dependent output voltage is monitored and regulated by the BCM Battery
Controller Module.
The output voltage is monitored and regulated by a temperature sensor. If there is a fault, the
FAULT output drops to 0 V.
Warning!
The power supply unit may only be used in the specially designed brackets and in a fireproof
!
cover (such as a panel housing).
Warning!
There is a risk of injury if the temperature sensor is not positioned between the batteries.
The temperature sensor is supplied with the power supply bracket and protects the batteries
!
against overheating. If the sensor is not positioned correctly, the batteries can overheat and
explode.
Position the temperature sensor between the batteries.
Figure 4.28: UPS 2416 A Universal Power Supply 24 V/6 A
Pos.
1 - 2
3
4 - 5
6
07.2020 | 12.0 | F.01U.028.089
1
2
3
4
5
6
7
1
Labeling
Connection
ACL | ACN
Mains supply
Protective ground
DC+ | DC-
26.76 V DC output plus/0 V DC output minus
FAULT
Mains fault output
8
LED
8