Chapter 3: Configuring the 1762sc-IF4OF4 for RSLogix 500
Table 3-3 lists the number of counts for each of the supported input channel data
ranges.
Table 3-3 (Output Channel Data Ranges)
Output
Output Value Condition
Range
4..20 mA
20.40 mA
20.00 mA
4.00 mA
3.92 mA
0..20 mA
20.40 mA
20.00 mA
0.00 mA
+/-10 V
11.00 VDC
10.00 VDC
-10.00 VDC
-11.00 VDC
0 to 5 V
5.50 VDC
5.00 VDC
0.00 VDC
0.00 VDC
0 to 10 V
11.00 VDC
10.00 VDC
0.00 VDC
0.00 VDC
1 to 5 V
5.50 VDC
5.00 VDC
1.00 VDC
0.00 VDC
3.4.3 Input Channel Configuration (Channels 4 and 5)
Channels 4 and 5 are current only channels. The table below describes the
configuration options for channels 4 and 5.
Raw/Prop EU
High Limit
32767
High Range
31176
Low Range
-32450
Low Limit
-32768
High Limit
32767
High Range
31482
Low
-32768
Limit/Range
High Limit
32767
High Range
29788
Low Range
-29788
Low Limit
-32768
High Limit
32767
High Range
26809
Low Range
-32768
Low Limit
-32768
High Limit
32767
High Range
26809
Low Range
-32768
Low Limit
-32768
High Limit
32767
High Range
26809
Low Range
-20853
Low Limit
-32768
User's Manual Pub. 0300247-01 Rev. D
3-5
PID
% FS
20400
16793 10250
20000
16383 10000
4000
0
0
3920
-82
-50
20400
16711 10200
20000
16383 10000
0
0
0
11000
17202 11000
10000
16383 10000
-10000 0
-10000
-11000 -819
-11000
5500
18021 11000
5000
16383 10000
0
0
0
0
0
0
11000
18021 11000
10000
16383 10000
0
0
0
0
0
0
5500
18431 11250
5000
16383 10000
1000
0
0
000
-4096
-2500