MULTIGATE-Profibus / multisys 1D3-ESDP
EndModule
Module="current 11.Harm"
EndModule
Module="current 13.Harm"
EndModule
Module="current 15.Harm"
EndModule
Module="current 17.Harm"
EndModule
Module="current 19.Harm"
EndModule
Module="powerfactor 3-phase"
EndModule
Module="max. lack of compensatory power"
EndModule
Module="temperature cabinet 1"
EndModule
Module="temperature cabinet 2"
EndModule
Module="temperature cabinet 3"
EndModule
Module="temperature cabinet 4"
EndModule
Module="temperature cabinet 5"
EndModule
Module="temperature cabinet 6"
EndModule
Module="stage status"
EndModule
Module="error status"
EndModule
11.2 Output data multicomp 96 LCD bus
No modules exist with output data, ie. data can only be retrieved via the Profibus.
11.3 Input data multicomp 96 LCD bus
The desired input data for the Profibus slave can be defined through any combination of the modules listed
below.
Module name
voltage PH-N L
voltage PH-PH L
apparent current L
apparent power L
active power L
reactive power L
cos Phi
lack of compensatory
power
actual target cos Phi
switched stage power
total stage power
total apparent power
total active power
total reactive power
frequency
Page - 30 -
0x41,0x83, 31
0x41,0x83, 32
0x41,0x83, 33
0x41,0x83, 34
0x41,0x83, 35
0x41,0x83, 36
0x41,0x83, 37
0x41,0x83, 38
0x41,0x83, 39
0x41,0x83, 40
0x41,0x83, 41
0x41,0x83, 42
0x41,0x83, 43
0x41,0x83, 44
0x41,0x83, 45
Config
Description
0x41,0x83, 0
Voltage PH-N L
0x41,0x83, 1
Voltage PH-PH L
0x41,0x83, 2
Apparent current
0x41,0x83, 3
Apparent power L
0x41,0x83, 4
Active power L
0x41,0x83, 5
Reactive power L
0x41,0x83, 6
cos Phi
0x41,0x83, 7
Insufficient compensation power
0x41,0x83, 8
Current target cos Phi
0x41,0x83, 9
Switched stage power
0x41,0x83, 10
Total stage power
0x41,0x83, 11
Total apparent power
0x41,0x83, 12
Total active power
0x41,0x83, 13
Total reactive power
0x41,0x83, 14
Frequency
Table 17: Input data multicomp 96 LCD bus
;
A
float
;
A
float
;
A
float
;
A
float
;
A
float
;
-
float
;
var
float
;
-
float
;
-
float
;
-
float
;
-
float
;
-
float
;
-
float
;
-
unsigned long
;
-
unsigned long
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Unit
Format
V
float
A
float
A
float
kVA
float
kW
float
kvar
float
float
kvar
float
float
kvar
float
kvar
float
kVA
float
kW
float
kvar
float
Hz
float
Version 1.0