This manual contains notes that must be observed for your personal DISCLAIMER safety and to prevent damage to the equipment. These notes are The contents of this document have been checked using the hardware identified by a warning sign or information symbol, depending on the and software described.
Page 4
To ensure proper and safe operation of the device, ensure that it is DANGEROUS VOLTAGE transported, stored, installed, assembled, and carefully operated and The applicable DIN/VDE regulations must be observed during maintained in accordance with the specifications. installation! If the device has any visible damage it is considered unfit for use and must be disconnected from the power supply! Troubleshooting, repairs Connection to the mains, commissioning and operation of the device and maintenance work may only be carried out at our plant or after...
NOTE If required, we will dispose of the device for you. Der multicount D5-xxx-MID is maintenance free. In case of damage (for example shipping, incorrect connection or storage) repairs may only be done by KBR GmbH.
MENU NAVIGATION TECHNICAL DATA Blue Go to next unit Nominal voltage U 3x230/400V (+/- 20%) Active energy, active power etc. Accuracy class B (1%) More information of unit Nominal frequency f 50Hz (60Hz on request) E.g. phase L1, L2, L3, total, Min. / Max values Operating temperature -25°...
Cable requirement >65A Direct connection Type: Wire (Cu), cross-section: 35mm², Current (I Outside-Ø 9,55 mm 0.02 A / 0.25 A / 0.5 A / 5 A / 75 A (5(75)) Current transformer /5A und /1A DISPLAY LANGUAGE Current /5A (I Display language can be selected between English and German 0.01 A / 0.05 A / 0.25 A / 5 A / 6 A (5(6)) (Deutsch).
1 = voltage Upon delivery, the address corresponds to the last four digits of the serial number. The address can only be changed via software (KBR eBus) TARIFF CONTROL Tariff changeover works with a 230V signal. Neutral cond. on clamp 5 (NE), outer cond.
Current transformer /1A Default settings ex-factory YYYY : 1A 1. S0 Output = Active Energy Import (12+13) adjustable in steps of 1 2. S0 Output = Reactive Energy Import (10 + 11) 3. S0 Output = Active Energy Export (8 + 9) Configuration of current transformer ratio 4.
Configuration of pulse length PEAK-CONTROL / THRESHOLD Threshold 1) Blue key to Adjustments 2) Red key to S0 Pulse Duration The following values can be chooses as a threshold: 3) Push service key briefly - Active Power - Reactive power - Apparent power 4) Adjust pulse length by blue key - Current total...
12) Saving: Push Service key for 5 seconds, until digits are not blinking Response time / release time 13) Red key to Threshold Time till ON The response and release time is adjustable between 0 and 9999 14) Push service key briefly seconds.
For security reasons a voltage change has to take place at both inputs MAXIMUM ACTIVE POWER: MEASUREMENT PERIOD E1 and E2. (only multicount D5-2-xxx-MID) Configuration of measurement period Normal mode Start new measurement 1) Blue key to Adjustments 2) Red key to Measurement period 3) Push service key briefly 4) Adjust time by blue key 0 = No voltage...
5) Perform reset: Push service key for 5 seconds RESET OF TARIFF REGISTER ERROR MESSAGES (only multicount D5-3P-xxx-MID) The multicount has a resettable tariff register. The resettable register is If an internal error appears, an error message is displayed. indicated by and arrow above the unit (kWh). F.F.0(00000000) No error, meter ok Reset tariff register...
F.F.0(xxxx1xxx) Error checksum Micro RAM. DATA BACKUP / POWER FAILURE F.F.0(xxxx2xxx) Error Micro STACK (Overflow). To prevent data loss in case of power failure, all relevant data are stored in non-volatile EEPROM. This takes place if voltage is falling below a F.F.0(xxxx3xxx) Error checksum Micro RAM and defined level.