DETERMINING THE NUMBER OF WIRES NEEDED (115 or 230 Volt installations).
Determine the wires needed in each step and add the number of wires from each step together to
determine total number of wires required. Total of 4 steps.
Step 1. Every model of 2300 / 2400 requires these wires:
(1) 12ga. Green ground wire
(1) 14ga Black L1 power wire for electronics power.
(1) 14ga. White for 115V neutral or red for 230V L2, for electronics power.
Step 2. If the dispenser is to be connected to a control console, and/or DCT Debit card reader remote
communication wires will be needed.
Single sided units:
OR
Two sided units:
Plus
DCT Debit card wires (1) 18ga. Blue, (1) 18ga. Violet and (1) 18ga. Gray wire all of them
Step 3. For Remote Dispensers a remote relay control wire will be required for each plumbed
product.
One product units: (1) Red 18ga. wire.
Two product Units: (1) Red, (1) Brown 18ga. wires.
Three product units: (1) Red, (1) Brown, (1) Blue 18ga wires.
Four product units: (1) Red, (1) Brown, (1) Blue, (1) Violet 18ga. wires.
Note:
3 product blenders only require 2 product control wires. The center, blended product will cause
both submerged pumps to turn on.
Note:
3+1 blenders require 3 product control wires. Two product control wires will be used to control
the 3 blended products. The 3rd product control wire will control the non-blended product,
usually diesel.
Step 4. For Self-Contained pumps a separate circuit and circuit breaker will be required for each
pumping unit motor. Place the pumping unit motor power circuit breakers on the opposite
phase from the dispenser's electronic power or on 230VAC. This will keep the dispenser's
electronic power free from electronic noise.
One Pumping Unit pumps: (1) Red for L2 Hot & (1) White 14ga. Neutral on 115V circuits
or (1) Black for L1 Hot for 230V circuits.
Two pumping unit pumps: (1) Red for L2 Hot, (1) Brown for L2 hot & (2) White 14ga.
Neutrals for 115V circuits or (2) Black for the other leg (L1) for 230V circuits.
Three pumping unit pumps: (1) Red for L2 Hot, (1) Brown for L2 hot, (1) Blue for L2 hot
& (3) White 14ga. Neutrals for 115V circuits or (3) Black for the other leg (L1) for 230V
circuits.
Four pumping unit pumps: (1) Red for L2 Hot, (1) Brown for L2 hot, (1) Blue for L2 hot,
(1) Violet for L2 Hot & (4) White 14ga. Neutrals for 115V circuits or (4) Black for the
other leg (L1) for 230V circuits.
Note:
Runs longer than 50ft. Will require larger wires. Size wires to minimize voltage loss or run the
motors on 230V circuits to minimize the current in the wires.

Wiring Instructions

(1) 18ga. Orange wire for communication positive.
(1) 18ga. Yellow wire for communications negative.
(2) 18ga. Orange wire for communication positive.
(2) 18ga. Yellow wire for communications negative.
twisted together at 3 turns per foot. Failure to twist these wires together
will result in improper operation and will void the equipment's limited
warranty.
17
105894 Rev G 12-6-16