Bennett Horizon 2 Series Installation Manual page 28

Electronic with 708 electronics
Table of Contents

Advertisement

Notes for Remote Wiring Diagram
1. All wiring must be installed and used in accordance with the national electrical code (NFPA #70,
Automotive and marine service code NFPA #30A), state and local electrical codes.
2. All wiring gauge is minimum required, stranded wire with THHN insulation must be used. Do not
reuse old wire from an existing installation.
3. Do not use PVC conduit. Use only rigid metal conduit.
4. Pull a Green 12 ga. stranded THHN ground wire through the junction box and wiring trough and
secure at grounding post near the terminal strip in the dispenser's electrical enclosure. Terminate
the other end at the main electrical service panel ground bar. Do not terminate at the neutral bar of
a sub-panel or rely on metal conduit for this ground connection. Each dispenser's grounding post
must be within 1 ohm resistance to earth ground potential. Do not use wire nuts on ground circuits,
use only compression type connectors.
5. Electronic power must be a dedicated circuit. The dispenser is factory wired to accept either
115VAC or 230VAC for its operation and may not be changed in the field. ( attempting to do this
will void the Bennett limited warranty) Electronic power for all dispensers at the installation must be
wired to the same AC line phase or damage will result to the dispensers. This will avoid a cross
phase condition on the remote relay control wires.
6. Use 15 Amp neutral breaking circuit breakers which are supplied by the customer.
Breaker Identification:
CB #1 Electronic Power - Hot for electronic power is 115VAC except for export codes which are
CB #3 Submerged pump motor product A.
CB #4 Submerged pump motor product B.
CB #5 Submerged pump motor product C.
CB #6 Submerged pump motor product D.
Note: No more than 2 dispensers per breaker. Only 1 submerged pump motor per breaker.
Electronic Power_____________________________560 Watts, 115V 60Hx or 230V 50Hz
Main Control Valve___________________________15 Watts, 115/230 VAC
Motor Relays________________________________1 H.P., 115/230 VAC
Motor______________________________________3/4 H.P., 115/230 VAC
Pulser______________________________________ INTRINSICALLY SAFE
Battery_____________________________________2.0 AMP Hours, 12 VDC
Pump Handle Switch___________________________INTRINSICALLY SAFE
230Vac.
Electrical Ratings
Figure 14B - 2300/2400 Series Remote
28
105894 Rev G 12-6-16