Installation of the RC Networks
4th Product: Connect the Violet 14ga. L1 - 120 or 240 VAC (HOT) wire from the 4th motor power
circuit breaker to the power board as indicated in the chart below. Connect the White 120VAC Neutral
or the Black L2-240VAC wire from the 4th motor power circuit breaker to the power board as indicated in
the chart below. NOTE: move the jumper wire on the dispenser power board from Tab T7 to Tab T8.
CAUTION: Set the motor voltage before applying power.
factory set for 120 volt operation. If 240 volt operation is needed, change the Voltage Selector
Switch on the motor from the low setting (120 Volt) to the high setting (240 Volt).
CAUTION: Use a separate 15 Amp. neutral breaking circuit breaker for each pump motor. Make
sure the pump motor is never on the same circuit breaker as any other power circuit for the
dispenser.
Note: TS refers to Power Board Terminal Strip followed by the terminal number.
Model Number
1st Product
2311, 2312
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2322, 2324
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2331 or 2332 Mixer
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2331 or 2332 Blender
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2342 or 2444 3+1
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
Blenders
TS 5
2422 or 2424
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2431 or 2432 Mixer
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2431 or 2432 Blender
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2433 or 2436
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2433 or 2436 Blender
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
2442 or 2444 3+1 Mix-
1st Circuit hot to TS 4.
ers
Neutral or 230Vac hot to
TS 5
2342 or 2444 3+1
1st Circuit hot to TS 4.
Blenders
Neutral or 230Vac hot to
TS 5
2444 or 2448
1st Circuit hot to TS 4.
Neutral or 230Vac hot to
TS 5
Wiring Self-Contained Motor Circuits
2nd Product
2nd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
2nd circuit hot to TS 8.
Neutral or 230Vac hot to
TS 9.
2nd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
The Diesel Product
(2nd) circuit hot to TS 8.
Neutral or 230Vac hot to
TS 9.
2nd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
2nd circuit hot to TS 8.
Neutral or 230Vac hot to
TS 9.
2nd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
2nd circuit hot to TS 8.
Neutral or 230Vac hot to
TS 9.
2nd circuit hot to TS 12.
Neutral or 230Vac hot to
TS 13.
2nd circuit hot to TS 8.
Neutral or 230Vac hot to
TS 9.
The Diesel Product
(2nd) circuit hot to TS 8.
Neutral or 230Vac hot to
TS 9.
2nd circuit hot to TS 8.
Neutral or 230Vac hot to
TS 9.
22
The pumps are shipped from the
3rd Product
4th Product
3rd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
3rd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
3rd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
3rd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
The Diesel Product (3rd)
4th circuit hot to TS 16.
circuit hot to TS 12.
Neutral or 230Vac hot to
Neutral or 230Vac hot to
TS 17.
TS 13.
3rd circuit hot to TS 16.
Neutral or 230Vac hot to
TS 17.
3rd circuit hot to TS 12.
4th circuit hot to TS 16.
Neutral or 230Vac hot to
Neutral or 230Vac hot to
TS 13.
TS 17.
105894 Rev G 12-6-16