4 OPERATION
(6) The [Edit station information] window is displayed. (Figure 4-8)
Figure 4-8 Edit Station Information Window
As the default display of the [Edit station information], the set station information is
displayed when the set station information is available, or the following is displayed when set
station information is not available (station information is not registered).
<Default value of station ID when station information is not registered>
Station number: 00
Refresh cycle monitor time: 0 ms
Station type: No selection
I/O area: Input disable status
Slot: Input disable status
Analog mode: Select disable status
To change or newly register station information, enter each piece of information and click the
OK
button. When you do not change station information, click the
Cancel
button.
The setting range of each piece of information to be entered on the [Edit station information]
window is shown on the next page.
4-12