1 SPECIFICATIONS

1.1 Use

Before using the IR.LINK module (model: LQE546), make sure that the IR.Station module
(model: LQS021) is connected. The IR.LINK module communicates digital data and analog
data with the IR.Station module. When a remote I/O is used, it implements higher-speed
communication. It also supports a function that starts up a task upon the detection of a change in
digital input.
1.2 Specifications

1.2.1 System specifications

Item
Model
Number of networks
Maximum number of IR.LINK
module that can be mounted in
the CPU
Mass

1.2.2 Line specifications

Item
Transmission method
Electrical interface
Number of stations
Communication
cable
LQE546
1 network/module
S10mini: 1 module/CPU (installed from the leftmost slot)
S10V: 1 module/CPU (installing from the leftmost slot is
not required.)
260 g
Serial (bit serial) transmission
RS-485
Up to 31 stations
Two pairs of shielded twisted-pair cables
Line type
Recommended cable: KPEV-SB 2P 0.5 mm
The distance depends on the transmission rate as follows:
Transmission rate ≤ 1.0 Mbps: Up to 240 m
Transmission rate ≤ 0.5 Mbps: Up to 480 m
Distance
Transmission rate ≤ 0.25 Mbps: Up to 800 m
Transmission rate ≤ 0.125 Mbps: Up to 1000 m
Terminal
6 points (M3 screw), fixed type
block
Specifications
Specifications
(Hitachi Cable, Ltd.)
1-2