Communication Errors; Table 6-3 Ir.link Module Network Error Table - Hitachi IR.LINK User Manual

Option for s10mini and s10v
Table of Contents

Advertisement

6 MAINTENANCE

6.3.3 Communication errors

(1) Network errors
When an error was found on the network of the IR.LINK module, the status error flag of the
NET status and the ALM of the S-register is turned ON and write error code (see table
below) into S-table.
In the S10mini, the following "error code" is displayed on the indicator of the CPU module.
In the S10V, an error code (ex. 0x7110) with "0x" appended to the beginning of the
following error code is displayed by selecting the error log from the S10V BASE SYSTEM.
Error code
7110
An undefined service was instructed.
7120
The data length is incorrect.
7130
The packet configuration is incorrect.
2010
An error was detected during CRC check.
2020
The station number is from 128 to 254 or
the received station number is incorrect.
2030
An undefined service was specified.
2040
The I-frame length is greater than or equal
to 137 bytes or the UI-frame length is
greater than or equal to 134 bytes.
2041
No I-frame exists in the I-response.
2042
An I-frame exists in the monitoring frame.
2050
Data link procedure error
2060
A timeout was detected (no response was
made from the slave station within the
specified time).
2061
The error could not be recovered by retry.
2070
No frame could be transmitted to the line or
an error was detected during frame
reception.
2080
Other errors

Table 6-3 IR.LINK Module Network Error Table

Explanation
• If this error recurs even after the CPU (or LPU) has been
reset once and then set to the original position again,
restart the IR.LINK module.
• If this error still recurs, replace the IR.LINK module.
• Check whether the network line is normal.
• Check whether SVPT setting matches station setting.
• If this error still recurs, replace the IR.LINK module.
• Power on the station again.
• Check whether the switches of the IR.LINK module and
station are set correctly.
• If this error still recurs even after the switches have been
set correctly, replace the station.
• Check the network line connection and terminating
resistor connection.
• Check whether SVPT setting matches station setting.
• If this error recurs even after the CPU (or LPU) has been
reset once and then set to the original position again,
restart the IR.LINK module.
• If this error still recurs, replace the IR.LINK module.
• If this error recurs even after the CPU (or LPU) has been
reset once and then set to the original position again,
restart the IR.LINK module.
• If this error still recurs, replace the IR.LINK module.