(2) Station errors
When an error is found in the IR.Station connected with the IR.LINK module, the error flag
of the NET status and the ALM of the S-register are turned on and the error code is written in
the S-table (shown below).
In the S10mini, the following "error code" is displayed on the indicator of the CPU module.
In the S10V, an error code (ex. 0x9001) with "0x" appended to the beginning of the
following error code is displayed by selecting the error log from the S10V BASE SYSTEM.
Error code
9001
The station is inactive.
9002
The station is in an abnormal state.
(An error was detected in the station.)
9003
The station is inactive and also in an
abnormal state.
8020
The initialization instruction was rejected.
8081
When the AUTO mode is specified, the
number of registered transfer bytes does not
match the response I/O size from the station.
8082
When a slot is specified, the number of
registered transfer bytes does not match the
response I/O size from the station.
For the starting method for the S10V BASE SYSTEM and the display method for error log
information in the S10V, refer to the "USER'S MANUAL BASIC MODULE (manual
number SVE-1-100)."

Table 6-4 IR.Station Module Error Table

Explanation
Power on the station again and
then reset the CPU (or LPU).
If this error still recurs, replace
the station.
SVPT setting does not match
station setting.
Set SVPT again to match
station setting. If this error
still recurs, replace the station.
6-11
6 MAINTENANCE
User response