5.1.2 Input signals (inverter (FR-E5NC) → → → → master unit)
The input signals to the master unit are indicated. (Output signals from inverter)
Device
Signal
No.
RX0
Forward running
RX1
Reverse running
RX2
Running (RUN)
RX3
Up to frequency (SU)
RX4
Overload (OL)
RX5
Reserved
RX6
Frequency detection (FU)
RX7
Alarm (A, B, C)
RX8
RX9
Reserved
RXA
RXB
RXC
Monitoring
Frequency setting command
RXD
(RAM)
Frequency setting command
RXE
2
(E
PROM)
Instruction code execution
RXF
completion
OFF : Other than forward running (during stop or reverse rotation)
ON : Forward running
OFF : Other than reverse running (during stop or forward rotation)
ON : Reverse running
On while the inverter is running. (Note)
Switched on when the output frequency reaches the set frequency ± Pr. 41.
Switched on when stall prevention is activated and switched off when stall prevention is
deactivated.
Reserved for the system.
Switched on when the output frequency reaches set frequency. (Note)
Switched on when the inverter's protective function is activated to stop the output. (Note)
Reserved for the system.
Switched on when the monitored value is set to RWr
switching on. Switched off when the monitor command (RYC) is switched off.
Switched on when the set frequency is written to the inverter by the frequency setting
command (RYD) switching on. Switched off when the frequency setting command
(RYD) is switched off.
Switched on when the set frequency is written to the inverter by the frequency setting
command (RYE) switching on. Switched off when the frequency setting command
(RYE) is switched off.
Switched on on completion of the processing corresponding to the instruction code
(RW
) which is executed when the instruction code execution request (RYF) switches
W2
on. Switched off when the instruction code execution completion (RXF) is switched off.
26
COMMUNICATION SPECIFICATIONS