Advertisement

4.4 Settings

Configuration is only possible in mains
operation or in the event of a battery fault.
No backwater may occur during configu-
ration.
The control unit makes two different con-
figurations possible for system operation.
When there is a corresponding water level
Running time mode (default setting)
in the pipe, the optical probe responds and
switches the pump on after a switch-on
delay. The pump runs for the time set.
When the level drops below the probe
level, the pump remains switched off. If
there is still a level message pending after
the running time has expired, the pump is
started again for the duration of the run-
ning time after a start-up delay.
When there is a corresponding water level
Run-on control
in the pipe, the optical probe responds and
switches the pump on after a switch-on
delay. When the pump runs, the water
level drops. The pump runs until the probe
indicates that the level has dropped to
below the switching level and the run-on
time has expired.
The following assignment of the LEDs is
Setting the configuration
used for shortened representation:
LED 1: "Power" LED LED 2:
"Alarm" LED
LED 3: "Level" LED
LED 4:
"Pump" LED
• Run-on time or running time
When the keys "Alarm" and "Pump" are
pressed for 5 seconds, the mode for con-
figuring run-on time or run time is rea-
ched. A signal is sounded and the
"Power" LED lights up. After both keys
have been released, the current setting
is shown on the basis of flashing LEDs.
The stage can be adjusted by pressing
the "Alarm" key. Every time the key is
pressed, the unit moves by on one stage
(see table). One or two flashing LEDs in-
dicate the stage set. The changed set-
ting is saved by pressing the "Pump" key;
this is accompanied by acoustic ackno-
wledgement in the form of a two-stage
4. Operating the Standard control unit
signal. If the "Pump" key is not pressed
within 20 seconds of selection being
made, configuration mode is quit auto-
matically without the change made being
saved.
Default setting is 5 seconds run time.
(Run-on)
flashing LEDs
running time (sec.) 5
• Switch-on delay
In order to reach the configuration setting
for switch-on delay, the mode for setting
(run-on) running time must be reached
first. Then press the "Alarm" and "Pump"
keys again briefly to reach configuration
mode for switch-on delay. A second
acoustic signal is sounded and the
"Power" and "Alarm" LEDs light up. After
both keys have been released, the cur-
rent setting is shown on the basis of flas-
hing LEDs.
The stage can be adjusted by pressing the
"Alarm" key. Every time the key is pres-
sed, the unit moves by on one stage (see
table). One or two flashing LEDs indicate
the stage set. The changed setting is
saved by pressing the "Pump" key; this is
accompanied by acoustic acknowledge-
ment in the form of a two-stage signal. If
the "Pump" key is not pressed within 20
seconds of selection being made, confi-
guration mode is quit automatically with-
out the change made being saved.
The default setting is for 2 seconds
switch-on delay
Switch-on
flashing LEDs
delay (sec.)
• Operating mode
In order to reach the configuration setting
for operating mode, the mode for setting
switch-on delay must be reached first.
Then press the "Alarm" and "Pump" keys
together again briefly to reach configu-
ration mode for operating mode. A third
acoustic signal is sounded and the
"Power", "Alarm" and "Level" LEDs light
up. After both keys have been released,
the current setting is shown on the basis
of flashing LEDs. The operating mode
1
1+2
2 2+3
3 3+4 4
10
15 20 25 30 35
1 1+2 2
2+3 3 3+4 4
0,5 1,0 1,5 2,0 3,0 4,0 5,0
7
can be adjusted by pressing the "Alarm"
key. Every time the key is pressed, the
operating mode is changed (see table).
A flashing LED indicates the stage set.
The changed setting is saved by pres-
sing the "Pump" key; this is accompanied
by acoustic acknowledgement in the
form of a two-stage signal. If the "Pump"
key is not pressed within 20 seconds of
selection being made, configuration
mode is quit automatically without the
change made being saved.
Run-time control is the default setting.
Operating mode
Run-on
flashing LEDs
control
Running time
1
2
control