Operation Mode Setting; Operation Mode Switching And Communication Startup Mode (Pr.79, Pr.340) - Mitsubishi Electric 800 Series Instruction Manual

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

4.2

Operation mode setting

4.2.1

Operation mode switching and communication startup mode (Pr.79, Pr.340)

 Operation mode switching conditions
Check the following before switching the operation mode.
• The inverter is at a stop.
• Both the STF and STR signals are off.
• The Pr.79 Operation mode selection setting is correct.
(Check the setting on the operation panel of the inverter.)
 Operation mode selection at power ON and at restoration from instantaneous power failure
The operation mode at power ON and at restoration from instantaneous power failure can be selected.
Set a value other than "0" in Pr.340 Communication startup mode selection to select the network operation mode.
After started in network operation mode, parameter write from the network is enabled.
(Refer to
page 89
for a program example for parameter write.)
NOTE
• Change of the Pr.340 setting is valid when powering on or resetting the inverter.
• Pr.340 can be changed with the operation panel independently of the operation mode.
• Ensure that the communication setting of the inverter is completed before setting Pr.340 ≠ "0".
• For the details of Pr.79 and Pr.340, refer to the FR-E800 Instruction Manual (Function).
34
INVERTER SETTING

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a8nc e

Table of Contents