System Configuration Example - Mitsubishi Electric 800 Series Instruction Manual

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

3.2

System configuration example

1.
Programmable controller side
Load the "RJ61BT11", "QJ61BT11N", "L26CPU-BT", "L26CPU-PBT", "LJ61BT11", "A1SJ61QBT11" or "A1SJ61BT11"
type CC-Link system master/local module on the main or extension base unit having the programmable controller CPU
used as the master station.
2.
Inverter side
Mount the plug-in option (FR-A8NC) on the inverter.
3.
Connect the master station of the CC-Link programmable controller unit to the CC-Link communication connector of FR-
A8NC with the CC-Link dedicated cable.
Manual of the CC-Link master station
RJ61BT11 type
CC-Link System Master/Local Module
User's Manual ...SH-081270ENG
QJ61BT11N type
CC-Link System Master/Local Module
User's Manual ...SH-080394E
L26CPU-BT type/L26CPU-PBT type/LJ61BT11 type
CC-Link System Master/Local Module
User's Manual ...SH-080895ENG
A1SJ61QBT11 type
CC-Link System Master/Local Module
User's Manual ...IB-66722
A1SJ61BT11 type
CC-Link System Master/Local Module
User's Manual ...IB-66721
NOTE
• When the CPU has automatic refresh function (example: QnA series CPU)
When the END instruction is executed by the programmable controller CPU, the buffer memory is automatically refreshed to
enable communication with a remote device.
• When the CPU does not have automatic refresh function (example: AnA series CPU)
Sequence ladder logic is configured to perform direct communication with the buffer memory of the master station and to
enable communication with a remote device
Master
station
QJ61BT11N,
etc.
Terminating
resistor
Power
supply
CC-Link dedicated cable
Inverter
Inverter
Up to 42
units can be
connected
when only
inverters are
connected
Motor
Remote device station
WIRING
3
Terminating
resistor
Motor
29