Safety Regulations/Emc; Mains Input Electrical Specifications - Huawei UPS5000-A-400 kVA User Manual

50 kva, pf 0.9
Hide thumbs Also See for UPS5000-A-400 kVA:
Table of Contents

Advertisement

UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)

8.3 Safety Regulations/EMC

8.4 Mains Input Electrical Specifications

Issue 03 (2020-01-10)
Safety Regulations/EMC
Safety regulations
EMC
Mains Input
Specifications
Input format
Rated input voltage
Input voltage range
Rated frequency
Input frequency
range
Input power factor
THDi
Copyright © Huawei Technologies Co., Ltd.
400 kVA
EN62040-1: 2013
IEC62040-1: 2013
EN62040-2
IEC62040-2
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
IEC61000-4-4
IEC61000-4-5
EN61000-4-6
IEC61000-4-8
IEC61000-4-11
400 kVA
Three-phase, four-wire, and PE wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
138–485 V AC
The UPS5000-A power is not derated at 305–485V AC and is
linearly derated at 305–138 V AC.
50 Hz or 60 Hz
40–70 Hz
> 0.99 (full load); > 0.98 (50% load)
< 3% (linear full load) or < 5% (non-linear load)
8 Technical Specifications