VLT® AutomationDrive FC 301/FC 302
Operating Guide
Enclosure
Power [kW (hp)]
22.0 (30.0)
C2
30.0 (40.0)
37.0 (50.0)
C3
18.5 (25.0)
22.0 (30.0)
C4
30.0 (40.0)
37.0 (50.0)
Table 43: 380–500 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
A1
0.37–1.5 (0.5–2.0)
A2
0.37–3.0 (0.5–4.0)
4.0 (5.0)
A3
5.5–7.5 (7.5–10.0)
A4
0.37-3.0 (0.5–4.0)
4.0 (5.0)
A5
0.37–3.0 (0.5–4.0)
4.0–7.5 (5.0–10.0)
B1
11–15 (15.0–20.0)
B2
18.5 (25.0)
22.0 (30.0)
B3
11–15 (15.0–20.0)
B4
18.5 (25.0)
22.0 (30.0)
30.0 (40.0)
C1
30.0 (40.0)
37.0 (50.0)
45.0 (60.0)
C2
55.0 (75.0)
75.0 (100.0)
C3
37.0 (50.0)
45.0 (60.0)
Danfoss A/S © 2021.01
Recommended
Recommended
fuse size
maximum fuse
gG-100
aR-160
aR-160
aR-200
aR-200
aR-250
gG-80
gG-150
aR-125
aR-160
aR-160
aR-200
aR-200
aR-250
Recommended
Recommended
fuse size
maximum fuse
gG-10
gG-25
gG-10
gG-25
gG-16
gG-16
gG-32
gG-10
gG-32
gG-16
gG-10
gG-32
gG-16
gG-40
gG-80
gG-50
gG-100
gG-63
gG-40
gG-63
gG-50
gG-125
gG-63
gG-80
gG-80
gG-160
gG-100
gG-160
aR-200
aR-250
aR-250
gG-100
gG-150
gG-160
gG-160
Recommended circuit
breaker Moeller
NZMB2-A250
NZMB2-A200
NZMB2-A250
Recommended circuit break-
er Moeller
PKZM0-16
PKZM0-25
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
AQ267037727118en-000101 / 130R0300 | 77
Specifications
Maximum trip
level [A]
250
150
250
Maximum trip
level [A]
16
25
25
25
25
63
100
50
100
160
250
150

Advertisement