VLT® AutomationDrive FC 301/FC 302
Operating Guide
Table 11: Speed Reference (Using a Manual Potentiometer)
Drive
50
+10 V
≈ 5kΩ
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 12: Speed Up/Down
Drive
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
Illustration 11: Speed Up/Down
28 | Danfoss A/S © 2021.01
Parameters
Function
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-11 Terminal 53 High Voltage
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
*=Default value
Notes/comments:
D IN 37 is an option.
Parameter
Function
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-13 Terminal 29 Digital Input
Parameter 5-14 Terminal 32 Digital Input
*=Default value
Notes/comments:
D IN 37 is an option.
Basic I/O Configuration
Setting
0.07 V*
10 V*
0 Hz
50 Hz
Setting
[8] Start*
[19] Freeze Reference
[21] Speed Up
[22] Speed Down
AQ267037727118en-000101 / 130R0300