Wiring Configuration: Speed - Danfoss VLT AutomationDrive FC 301 Operating Manual

0.25–75 kw, enclosure sizes a-c
Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT® AutomationDrive FC 301/FC 302
Operating Guide

6.1.4 Wiring Configuration: Speed

Table 9: Analog Speed Reference (Voltage)
Drive
50
+10 V
+
A IN
53
A IN
54
COM
55
-
A OUT
42
0–10 V
COM
39
U - I
A53
Table 10: Analog Speed Reference (Current)
Drive
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
4-20mA
COM
39
U - I
A53
Danfoss A/S © 2021.01
Parameters
Function
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-11 Terminal 53 High Voltage
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
*=Default value
Notes/comments:
D IN 37 is an option.
Parameters
Function
Parameter 6-12 Terminal 53 Low Current
Parameter 6-13 Terminal 53 High Current
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
*=Default value
Notes/comments:
D IN 37 is an option.
Basic I/O Configuration
Setting
0.07 V*
10 V*
0 Hz
50 Hz
Setting
4 mA*
20 mA*
0 Hz
50 Hz
AQ267037727118en-000101 / 130R0300 | 27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents