5.3 System Set-up

Procedure
1.
Perform automatic motor adaption (AMA):
a.
Set the basic motor parameters before performing AMA.
Table 6: Basic Parameters to be Checked before AMA
Parameter 1-20 Motor Power [kW]/parameter 1-21 Motor Power
[hp]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
Parameter 1-26 Motor Cont. Rated
Parameter 1-39 Motor Poles
b.
Optimize the compatibility between motor and drive via parameter 1-29 Automatic Motor Adaptation (AMA).
2.
Check motor rotatation.
3.
If encoder feedback is used, perform the following steps:
a.
Select [0] Speed open loop in parameter 1-00 Configuration Mode.
b.
Select [1] 24V encoder in parameter 7-00 Speed PID Feedback Source.
c.
Press [Hand On].
d.
Press [▹] for positive speed reference (parameter 1-06 Clockwise Direction at [0]).
e.
In parameter 16-57 Feedback [RPM], check that the feedback is positive.
24 | Danfoss A/S © 2021.01