GE AF-650 GP Programming Manual page 83

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

3
t jog s x n s RPM
Par
. C − 22 =
log speed
Δ
C-23 Quick Stop Decel Time
Range:
3.00 s*
[0.01 - 3600.00 s]
t Qstop s x n s RPM
Par
. C − 23 =
jog ref
Δ
3.5.3 C-3# Frequency Setting 2 and 3
Parameters to configure Frequency Settings 2 and 3.
C-30 Frequency Command 2
Option:
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Frequency input 29
82
(
par
. C − 21 )
RPM
Function:
Enter the quick–stop decel time from the synchronous motor speed to 0 RPM. Ensure that no resultant
over-voltage will arise in the inverter due to regenerative operation of the motor required to achieve the
given decel time. Ensure also that the generated current required to achieve the given decel time does
not exceed the current limit (set in par. F-43 Current Limit). Quick-stop is activated by means of a signal
on a selected digital input, or via the serial communication port.
(
. C − 21 )
par
RPM
Function:
Select the reference input to be used for the second reference signal. par. F-01 Frequency Setting 1, par.
C-30 Frequency Command 2 and par. C-34 Frequency Command 3 define up to three different reference
signals. The sum of these reference signals defines the actual reference.
AF-650 GP Programming Guide