LC-11 Comparator Operator
Array [6]
Option:
[0] *
<
≈ (equal)
[1]
[2]
>
LC-12 Comparator Value
Array [6]
Range:
0*
[-100000.000 - 100000.000]
3.19.3 LC-2# Timers
Parameters to configure the Logic Controller (LC) timers. Timers are used to define when an event can occur.
LC-20 Logic Controller Timer
Range:
0.000*
[0.000 - 0.000]
3.19.4 LC-4# Logic Rules
Parameters to configure the Logic Controller (LC) Logic Rules. Logic Rules are used to define what conditions need to be met for the LC to step to the next event.
LC-40 Logic Rule Boolean 1
Array [6]
Option:
[0] *
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
Remote ref. active [181] High when par. F-02 Operation Method= [1] Remote or [0] Linked to hand/auto,
while the Keypad is in Auto mode.
Start command [182] High when there is an active start command, and no stop command.
Drive stopped [183] A stop command ( Jog, Stop, Qstop, Coast) is issued – and not from the Logic Controller
itself.
Drive in hand mode [185] High when the frequency converter is in hand mode.
Drive in auto mode [186] High when the frequency converter is in auto mode.
Function:
Select < [0] for the result of the evaluation to be TRUE, when the variable selected in par. LC-10 Comparator
Operand is smaller than the fixed value in par. LC-12 Comparator Value. The result will be FALSE, if the
variable selected in par. LC-10 Comparator Operand is greater than the fixed value in par. LC-12 Com-
parator Value.
Select ≈ [1] for the result of the evaluation to be TRUE, when the variable selected in par. LC-10 Comparator
Operand is approximately equal to the fixed value in par. LC-12 Comparator Value.
Select > [2] for the inverse logic of option < [0].
Function:
Enter the 'trigger level' for the variable that is monitored by this comparator. This is an array parameter
containing comparator values 0 to 5.
Function:
Enter the value to define the duration of the FALSE output from the programmed timer. A timer is only
FALSE if it is started by an action (i.e. Start timer 1 [29]) and until the given timer value has elapsed.
Function:
Select the first boolean (TRUE or FALSE) input for the selected logic rule.
See par. LC-01 Start Event ([0] - [61]) and par. LC-02 Stop Event ([70] - [75]) for further description.