[0] *
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
3.10.2 O-1# Control Settings
Parameters to configure the option control word profile.
O-10 Control Word Profile
Select the interpretation of the control and status words corresponding to the installed network. Only the selections valid for the network installed in slot A will
be visible in the Keypad display.
For guidelines in selection of GE Drive profile [0] and PROFIdrive profile [1] please refer to the Serial communication via RS 485 Interface section.
For additional guidelines in the selection of PROFIdrive profile [1], ODVA [5] and CANopen DSP 402 [7], please refer to the Operating Instructions for the installed
network.
Option:
[0] *
Drive Profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
O-13 Configurable Status Word STW
Option:
[0]
No function
[1] *
Profile Default
[2]
Alarm 68 Only
[3]
Trip excl Alarm 68
[16]
T37 DI status
O-14 Configurable Control Word CTW
Option:
[0]
None
[1] *
Profile default
[2]
CTW Valid, active low
The content of the extended diagnosis frame is as follows:
Byte
Content
0 - 5
Standard DP Diagnose Data
6
PDU length xx
7
Status type = 0x81
8
Slot = 0
9
Status info = 0
10 - 13
par. DR-92 Warning Word
14 - 17
par. DR-03 Status Word
18 - 21
par. DR-90 Alarm Word
22 - 23
par. PB-53 Profibus Warning
Word
Enabling diagnosis may cause increased bus traffic. Diagnosis functions are not supported by all network
types.
Function:
Function:
This parameter enables configuration of bits 12 – 15 in the status word.
Function corresponds to the profile default selected in par. O-10 Control Word Profile.
Only set in case of an Alarm 68.
Set in case of a trip, except if the trip is executed by an Alarm 68.
The bit indicates the status of terminal 37.
"0" indicates T37 is low (safe stop)
"1" indicates T37 is high (normal)
Function:
Selection of control word bit 10 if it is active low or active high
AF-650 GP Programming Guide
Description
Standard DP Diagnose Data
Header of extended diagnostic data
Header of extended diagnostic data
Header of extended diagnostic data
Header of extended diagnostic data
warning word
status word
alarm word
Communication warning word (Profibus)
3
117

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents