AN-40 Terminal X30/12 Low Voltage
Range:
0.07 V*
[0.00 - par. AN-41 V]
AN-41 Terminal X30/12 High Voltage
Range:
10.00 V*
[par. AN-40 - 10.00 V]
AN-44 Term. X30/12 Low Ref./Feedb. Value
Range:
0.000 Unit*
[-1000000.000 to par. AN-45]
AN-45 Term. X30/12 High Ref./Feedb. Value
Range:
1500.000*
[Par. AN-44 to 100000.000]
AN-46 Term. X30/12 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
3.8.6 AN-5# Analog Output 42
Parameters to configure the scaling and limits for Analog Output 1 (terminal 42)
AN-50 Terminal 42 Output
Option:
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
Function:
Sets the analog input scaling value to correspond to the low reference/feedback value set in par.
AN-44 Term. X30/12 Low Ref./Feedb. Value.
Function:
Sets the analog input scaling value to correspond to the high reference/feedback value set in par.
AN-45 Term. X30/12 High Ref./Feedb. Value.
Function:
Sets the analog output scaling value to correspond to the low voltage value set in par. AN-40 Terminal
X30/12 Low Voltage.
Function:
Sets the analog input scaling value to correspond to the high voltage value set in par. AN-41 Terminal
X30/12 High Voltage.
Function:
st
A 1
order digital low pass filter time constant for suppressing electrical noise on terminal X30/12.
par. AN-46 Term. X30/12 Filter Time Constant cannot be changed while the motor is running.
Function:
Select the function of Terminal 42 as an analog current output. Depending on the selection the output is
either a 0-20 mA or 4-20 mA output. The current value can be read out in Keypad in par. DR-65 Analog
Output 42 [mA].
When no signal on the analog output.
0 Hz = 0 mA; 100 Hz = 20 mA.
par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
Motor current 0 - 20 mA: Value is taken from par. DR-37 Drive Max. Current. Inverter max. current (160%
current) is equal to 20 mA.
The torque setting is related to setting in par. F-40 Torque Limiter (Driving)
The torque is related to the motor torque setting.
Taken from par. P-07 Motor Power [kW].
Taken from par. F-53 Maximum Reference. 20 mA = value in par. F-53 Maximum Reference
Torque reference related to 160% torque.
In relation to par. F-03 Max Output Frequency 1.
AF-650 GP Programming Guide
3