AN-53 Terminal 42 Output Bus Control
Range:
0.00 %*
[0.00 - 100.00 %]
AN-54 Terminal 42 Output Timeout Preset
Range:
0.00 %*
[0.00 - 100.00 %]
3.8.7 AN-6# Analog Output X30/8
Parameters to configure the scaling and limits for Analog Output 1 associated with OPCGPIO General Purpose Field Installed Option Module.
AN-60 Terminal X30/8 Output
Option:
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[119]
Torque % lim
[130]
Output freq. 4-20mA
Function:
Holds the level of Output 42 if controlled by bus.
Function:
Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in par. AN-50 Terminal 42 Output the output
will preset to this level.
Function:
Select the function of Terminal X30/8 as an analog current output. Depending on the selection the output
is either a 0-20 mA or 4-20 mA output. The current value can be read out in Keypad in par. DR-65 Analog
Output 42 [mA].
When no signal on the analog output.
0 Hz = 0 mA; 100 Hz = 20 mA.
par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
Motor current 0 - 20 mA: Value is taken from par. DR-37 Drive Max. Current. Inverter max. current (160%
current) is equal to 20 mA.
The torque setting is related to setting in par. F-40 Torque Limiter (Driving).
The torque is related to the motor torque setting.
Taken from par. P-07 Motor Power [kW].
Taken from par. F-53 Maximum Reference. 20 mA = value in par. F-53 Maximum Reference
Torque reference related to 160% torque.
In relation to par. F-03 Max Output Frequency 1.
Torque % lim: Torque reference. par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
0 Hz = 4 mA, 100 Hz = 20 mA