Preset ramp bit
Ramp 1
Ramp 2
Ramp 3
Ramp 4
[36]
Mains failure inverse
[41]
Latched Precise Stop inverse
3
[55]
DigiPot Increase
[56]
DigiPot Decrease
[57]
DigiPot Clear
[60]
Counter A
[61]
Counter A
[62]
Reset Counter A
[63]
Counter B
[64]
Counter B
[65]
Reset Counter B
[70]
Mech. Brake Feedback
[71]
Mech. Brake Feedback inv.
[80]
PTC Card 1
E-51 Terminal 27 Mode
Option:
[0] *
Input
[1]
Output
Please not that this parameter cannot be adjusted while the motor is running.
E-52 Terminal 29 Mode
Option:
[0] *
Input
[1]
Output
This parameter cannot be adjusted while the motor is running.
E-53 Terminal X30/2 Digital Input
Option:
[0] *
No operation
[1]
Reset
[2]
Coast inverse
[3]
Coast and reset inv
[4]
Quick stop inverse
[5]
DC-brake inverse
[6]
Stop inverse
[8]
Start
[9]
Latched start
[10]
Reversing
[11]
Start reversing
[12]
Enable start forward
[13]
Enable start reverse
70
Activates par. SP-10 Line failure. Mains failure inverse is active in the Logic .0. situation.
Sends a latched stop signal when the precise stop function is activated in par. H-83 Precise Stop Func-
tion. The Latched Precise stop inverse function is available for terminals 18 or 19.
INCREASE signal to the Digital Potentiometer function described in parameter group F-9#
DECREASE signal to the Digital Potentiometer function described in parameter group F-9#
Clears the Digital Potentiometer reference described in parameter group F-9#
(Terminal 29 or 33 only) Input for increment counting in the LC counter.
(Terminal 29 or 33 only) Input for decrement counting in the LC counter.
Input for reset of counter A.
(Terminal 29 or 33 only) Input for increment counting in the LC counter.
(Terminal 29 or 33 only) Input for decrement counting in the LC counter.
Input for reset of counter B.
Brake feedback for hoisting applications
Inverted brake feedback for hoisting applications
All Digital Inputs can be set to PTC Card 1 [80]. However, only one Digital Input must be set to this choice.
Function:
Defines terminal 27 as a digital input.
Defines terminal 27 as a digital output.
Function:
Defines terminal 29 as a digital input.
Defines terminal 29 as a digital output.
Function:
This parameter is active when option module OPCGPIO General Purpose I/O Option Module is installed in
the frequency converter.
AF-650 GP Programming Guide