GE AF-650 GP Programming Manual page 21

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

2.1.8 Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up procedure using Keypad (read table from
left to right). The example applies to open loop applications:
2
Press
par. K-01 Language
par. K-02 Motor Speed Unit
par. P-02 Motor Power [HP] or par. P-07 Motor
Power [kW]
par. F-05 Motor Rated Voltage
par. F-04 Base Frequency
par. P-03 Motor Current
par. P-06 Base Speed
par. F-01 Frequency Setting 1
par. F-02 Operation Method
par. F-07 Accel Time 1
par. F-08 Decel Time 1
par. F-10 Electronic Overload
par. F-15 Motor Speed High Limit [Hz] or par.
F-17 Motor Speed High Limit [RPM]
par. F-16 Motor Speed Low Limit [Hz] or par.
F-18 Motor Speed Low Limit [RPM]
par. H-08 Reverse Lock
par. P-04 Auto Tune
20
Quick Start
Set language
Set motor speed in Hz or RPM
Set Motor nameplate power
Set Nameplate voltage
Set Nameplate frequency
Set Nameplate current
Set Nameplate speed in RPM
Set reference source
Select which reference site to activate
Set the accel time with reference to synchronous motor speed, n
Set the decel time time with reference to synchronous motor speed,
n
s
Set motor thermal protection
Set motor speed high limit in Hz or RPM
Set motor speed low limit in Hz or RPM
Set allowed rotation direction
Set desired auto tune function. Enable complete auto tune is rec-
ommended
AF-650 GP Programming Guide
s

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents