The reset is carried out by pressing [OK].
ID-07 Reset Running Hours Counter
Option:
[0] *
Do not reset
[1]
Reset counter
3
ID-08 Number of Starts
Range:
0*
[0 - 2147483647]
NB!
This parameter will be reset when resetting par. ID-07 Reset Running Hours Counter.
3.16.2 ID-1# Data Trending Settings
Data Log Settings enables continous logging of up to 4 data sources (par. ID-10) at individual rates (par. ID-11). A trigger event (Par. ID-12) and window (par. ID-14)
are used to start and stop the logging conditionally.
ID-10 Trending Source
Array [4]
Option:
ID-11 Trending Interval
Range:
1 ms*
[1 - 86400000 ms]
ID-12 Trigger Event
Select the trigger event. When the trigger event occurs, a window is applied to freeze the log. The log will then retain a specified percentage of samples before
the occurrence of the trigger event (par. ID-14 Samples Before Trigger).
Choices are described under E-## Digital Output.
Option:
[0] *
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
136
Function:
Select Reset [1] and press [OK] to reset the Running Hours counter to zero (see par. ID-01 Running
Hours). This parameter cannot be selected via the serial port, RS 485.
Select Do not reset [0] if no reset of the Running Hours counter is desired.
Function:
This is a read out parameter only. The counter shows the numbers of starts and stops caused by a normal
Start/Stop command and/or when entering/leaving sleep mode.
Function:
Select which variables are to be logged.
Function:
Enter the interval in milliseconds between each sampling of the variables to be logged.