GE AF-650 GP Programming Manual page 105

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

[119]
Torque % lim
[130]
Output freq. 4-20mA
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
3
[133]
Motor cur. 4-20mA
[134]
Torq.% lim 4-20 mA
[135]
Torq.% nom 4-20 mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[138]
Torque 4-20mA
[139]
Bus ctrl. 0-20 mA
[140]
Bus ctrl. 4-20 mA
[141]
Bus ctrl 0-20mA t.o.
[142]
Bus ctrl 4-20mA t.o.
[149]
Torque % lim 4-20mA
[150]
Max Out Fr 4-20mA
AN-51 Terminal 42 Output Min Scale
Range:
0.00 %*
[0.00 - 200.00 %]
AN-52 Terminal 42 Output Max Scale
Range:
100.00 %*
[0.00 - 200.00 %]
mA
desired maximum current x
20
/
104
Torque % lim: Torque reference. par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
0 Hz = 4 mA, 100 Hz = 20 mA
par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20 mA
par. F-50 Reference Range [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
Feedback 4-20mA: par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20 mA
par. F-50 Reference Range [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
Value is taken from par. DR-37 Drive Max. Current. Inverter max. current (160% current) is equal to 20 mA.
The torque setting is related to setting in par. F-40 Torque Limiter (Driving).
The torque setting is related to the motor torque setting.
Taken from par. P-07 Motor Power [kW]
Taken from par. F-53 Maximum Reference. 20 mA = Value in par. F-53 Maximum Reference.
Torque reference related to 160% torque.
An output value set from Network process data. The output will work independently of internal functions
in the frequency converter.
An output value set from Network process data. The output will work independently of internal functions
in the frequency converter.
par. H-74 Warning Reference Low defines the behaviour of the analog output in case of bus time-out.
par. H-74 Warning Reference Low defines the behaviour of the analog output in case of bus time-out.
Torque % Lim 4-20mA: Torque reference. par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20mA
par. F-50 Reference Range [-Max - Max] -100% = 4 mA; 0% = 12mA; +100% = 20mA
In relation to par. F-03 Max Output Frequency 1.
Function:
Scale for the minimum output (0 or 4 mA) of the analogue signal at terminal 42.
Set the value to be the percentage of the full range of the variable selected in par. AN-50 Terminal 42
Output.
Function:
Scale the maximum output of the selected analog signal at terminal 42. Set the value to the maximum
value of the current signal output. Scale the output to give a current lower than 20 mA at full scale; or 20
mA at an output below 100% of the maximum signal value. If 20 mA is the desired output current at a
value between 0 - 100% of the full-scale output, programme the percentage value in the parameter, i.e.
50% = 20 mA. If a current between 4 and 20 mA is desired at maximum output (100%), calculate the
percentage value as follows:
100 %
20
i
e
mA
x
.
. 10
:
100 = 200 %
10
AF-650 GP Programming Guide