GE AF-650 GP Programming Manual page 130

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Bit:
Meaning:
0
Connection with DP-master is not ok
1
Not used
2
FDL (Field-bus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Baudrate search
6
PROFIBUS ASIC is not transmitting
7
Initializing of PROFIBUS is not ok
8
Frequency converter is tripped
9
Internal CAN error
10
Wrong configuration data from PLC
11
Wrong ID sent by PLC
12
Internal error occured
13
Not configured
14
Timeout active
15
Warning 34 active
PB-63 Actual Baud Rate
Option:
[0]
9,6 kbit/s
[1]
19,2 kbit/s
[2]
93,75 kbit/s
[3]
187,5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255] *
No baudrate found
PB-64 Device Identification
Range:
0*
[]
PB-65 Profile Number
Range:
0*
[]
NB!
This parameter is not visible via Keypad.
PB-67 Control Word 1
Range:
0*
[0 - 65535]
PB-68 Status Word 1
Range:
0*
[0 - 65535]
Function:
This parameter displays the actual Profibus baud rate. The Profibus Master automatically sets the baud
rate.
Function:
This parameter displays the device identification. Please refer to the Operating Instructions for Profibus,
for further explanation.
Function:
This parameter contains the profile identification. Byte 1 contains the profile number and byte 2 the
version number of the profile.
Function:
This parameter accepts the Control Word from a Master Class 2 in the same format as PCD 1.
Function:
This parameter delivers the Status Word for a Master Class 2 in the same format as PCD 2.
AF-650 GP Programming Guide
3
129