3.17.5 DR-6# Inputs/Outputs
Parameters to view the digital and analog I/O status values.
DR-60 Digital Input
Range:
0*
[0 - 1023]
DR-61 Terminal 53 Switch Setting
Option:
[0] *
Current
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
DR-62 Analog Input 53
Range:
0.000*
[-20.000 - 20.000]
Function:
View the signal states from the active digital inputs. Example: Input 18 corresponds to bit no. 5, '0' = no
signal, '1' = connected signal. Bit 6 works in the opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4 (OPCGPIO)
Bit 8
Digital input GP I/O term. X30/3 (OPCGPIO)
Bit 9
Digital input GP I/O term. X30/2 (OPCGPIO)
Bit 10-63
Reserved for future terminals
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Function:
View the setting of input terminal 53. Current = 0; Voltage = 1.
Function:
View the actual value at input 53.
AF-650 GP Programming Guide
DI T-33
DI T-32
DI T-29
DI T-27
DI T-19
DI T-18
DI T-37
DI X30/4 (OPCCPIO)
DI X30/3 (OPCCPIO)
DI X30/2 (OPCCPIO)
DI
DI
DI
DI
DI
DI
DI
130BA894.10