Multiple Load Connection With Distribution Terminals; Grounding Outputs - TDK-Lambda GENESYS GEN 2400W Series Technical Manual

1u programmable dc power supplies
Hide thumbs Also See for GENESYS GEN 2400W Series:
Table of Contents

Advertisement

Power
Supply
-
-
+
+
Figure 3-12: Multiple Loads Connection, Radial Distribution, Local Sense
3.9.10

Multiple Load Connection with Distribution Terminals

If remotely located output distribution terminals are used, the power supply output terminals should be
connected to the distribution terminals by a pair of twisted and/or shielded wires. Each load should be separately
connected to the remote distribution terminals (see Figure 3-13).
If remote sensing is required, the sensing wires should be connected to the distribution terminals or at the most
critical load.
Power
Supply
-
-
+
+
Figure 3-13: Multiple Load Connection with Distribution Terminal
3.9.11

Grounding Outputs

Either the positive or negative output terminals can be grounded. To avoid noise problems caused by common-
mode current flowing from the load to ground, it is recommended to ground the output terminal as close as
possible to the power supply chassis ground.
Always use two wires to connect the load to the power supply regardless of how the system is grounded.
Models up to 60VDC Rated Output voltage shall not float outputs more
than +/-60VDC above/below chassis ground. Models with > 60VDC
Rated Output voltage shall not float outputs more than +/-600VDC
Load lines, twisted pair,
shortest length possible.
+V
-V
Rem.sense
Local sense
Local sense
Rem.sense
Fig.3-13: Multiple loads connection, radial distribution, local sense
+V
-V
Rem.sense
Local sense
Local sense
Rem.sense
Fig.3-14: Multiple loads connection with distribution terminal
above/below chassis ground.
83-517-000 Rev. A
Distribution terminal
+V
-V
WARNING
33
+
Load#1
+
Load#2
+
Load#3
+
Load#1
+
Load#2
+
Load#3

Advertisement

Table of Contents
loading

Table of Contents