5.16 DAISY-CHAIN CONNECTION

It is possible to configure a multiple power supply system to shut down all the units when a fault condition occurs
in one of the units. When the fault is removed, the system recovers according to its setting to Safe-Start mode
or Auto-Restart.
Setup DIP-switch SW1-5 should be set to the DOWN position to enable the Daisy-Chain Shut-Off operation.
Other SW1 positions can be set according to the application requirements.
If a fault occurs in one of the daisy-chained units, its PS_OK signal will be set to a low level and the unit front
panel display will indicate the fault. The other units in the daisy-chain will Shut-Off and their front panel display
1.
In parallel operation, the AC Supply should be applied to the Master unit first and then to the
each of the Slave units.
The above sequence is not required if the units are connected for Daisy-Chain Shut-Off
2.
operation.
displays will indicate "SO". When the fault condition is removed, the units will recover to their last setting
according to their Safe-Start or Auto-Restart setting. Figure 5-6 shows a connection of three units, however the
same connection method applies to systems with a larger number of units.
-S
-LS
To J1-10
SLAVE#2
MASTER
POWER SUPPLY
POWER SUPPLY
J1-25
J1-8 J1-12
J1-10
SLAVE#1
To J1-23
SLAVE#2
POWER SUPPLY
POWER SUPPLY
-S
-LS +LS
Figure 5-4: Parallel Connection with Local Sensing
Fig.5-4: Parallel connection with local sensing
operation. Disconnection may cause damage to the power supply.
+S
-S
Twisted
pair
-S
+S
As short as possible
+ V
-
V
J1-25
J1-12
P
P
IPGM
IPGM_RTN
J1-10
J1-23
+ V
-
V
-LS
+LS
+S
Figure 5-5:
Parallel Operation with Remote Sensing
83-517-000 Rev. A
+S
+LS
As short as possible
+
V
-
V
J1-12
P
P
IPGM
IPGM_RTN
J1-23
+
V
-
V
+S
CAUTION
+S
Twisted
pair
LOAD
-S
NOTE
52
Twisted
pair
LOAD
CAUTION
Make sure that the connection
–Vo
between
terminals is
reliable to avoid disconnection
during operation.
Disconnection may cause
damage to the power supply.