Chapter 1 General Information; User Manual Content; Introduction; General Description - TDK-Lambda GENESYS GEN 2400W Series Technical Manual

1u programmable dc power supplies
Hide thumbs Also See for GENESYS GEN 2400W Series:
Table of Contents

Advertisement

CHAPTER 1 GENERAL INFORMATION

1.1 USER MANUAL CONTENT

This User's Manual contains the operating instructions, installation instructions and specifications of the
TM
Genesys
2400W power supply series. The instructions refer to the standard power supplies, including the
built-in RS-232/RS-485 serial communication. For information related to operation with the optional LAN, IEEE
or USB programming, refer to specific Programming Interface User Manual (TDK-Lambda P/N 83-034-100
(LAN), P/N 83-030-200 (IEEE) and P/N 83-033-800 (USB)).

1.2 INTRODUCTION

1.2.1

General Description

TM
Genesys
power supplies are wide output range, high performance switching power supplies. The Genesys
series is power factor corrected and operates from worldwide AC voltage range. Output voltage and current are
continuously displayed and LED indicators show the complete operating status of the power supply. The front
panel controls allow the user to set the output parameters, the protection levels (Over-Voltage protection, Under-
Voltage limit and Foldback) and Preview the settings. The rear panel includes the necessary connectors to
control and monitor the power supply operation by remote analog signals or by the built-in serial communication
(RS-232/RS-485). LAN,IEEE and USB programming and Isolated-Analog programming/monitoring are optional.
1.2.2

Models Covered by this Manual

1.2.3

Features and Options

Constant-Voltage / Constant-Current with automatic crossover.
Active Power Factor correction.
Single Phase or Three Phase options.
Embedded Microprocessor Controller.
Built-in RS-232/RS-485 Interface.
Voltage & Current high resolution adjustment by digital encoders.
High accuracy programming/readback-16 bit.
Software Calibration (no internal trimmers / potentiometers).
Last Setting Memory.
Independent Remote ON/OFF (opto-isolated) and remote Enable/Disable.
Parallel operation (Master/Slave) with Active current sharing.
Remote sensing to compensate for voltage drop of power leads.
Voltage range
Model
GEN 8 - 300
0 - 8
GEN 10 - 240
0 - 10
GEN 16 - 150
0 - 16
GEN 20 - 120
0 - 20
GEN 30 - 80
0 - 30
GEN 40 - 60
0 - 40
GEN 60 - 40
0 - 60
GEN 80 - 30
0 - 80
GEN 100 - 24
0 - 100
GEN 150 - 16
0 - 150
GEN 300 - 8
0 - 300
GEN 600 - 4
0 - 600
Table 1-1: Models Covered by this Manual
83-517-000 Rev. A
Current range
(V)
(A)
0 - 300
0 - 240
0 - 150
0 - 120
0 - 80
0 - 60
0 - 40
0 - 30
0 - 24
0 - 16
0 - 8
0 - 4
15
TM

Advertisement

Table of Contents
loading

Table of Contents