Commissioning
4.4 Commissioning with the BOP-2
4.4.4

Changing parameter values.

Use BOP-2 to change your inverter settings, by selecting the appropriate parameter number
and changing the parameter value. Parameter values can be changed in the menu
"PARAMS" and in the menu "SETUP"
Select the parameter number
● If the parameter number flashes in the display, you have two options of selecting the
● Accept the parameter number by briefly pressing the OK key.
Changing a parameter value
● If the parameter value flashes in the display, you have two options of changing the value:
● Accept the parameter value by briefly pressing the OK key.
Saving settings so that they are not lost when the power fails
The inverter immediately saves all changes which you made using the BOP-2 so that they
are protected against power failure.
70
number:
– Using the arrow keys, scroll to the required parameter number.
– Press the OK key for longer than two seconds and enter the required parameter
number digit for digit:
– Changing the parameter value using the arrow keys.
– Press the OK key for longer than two seconds and enter the required value digit for
digit:
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA