Parameter
P20162 = 430
P20032 = 5
P20033 = 440
P20159 = 5.0
P20158 = 722.0
P20030 [0] = 20160
P20030 [1] = 722.1
P0840 = 20031
Explanation of the example using the ON/OFF1 command
Open the default signal interconnection for BICO parameterization
After selecting the digital inputs as command source (P0700 = 2), digital input 0 is
automatically interconnected to the ON/OFF1 command. Parameter P0840[0] has the value
722.0.
Figure 1-5
The setting P0701 = 0 means that this interconnection is disconnected.
Figure 1-6
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Description
Run sequence of the time block within runtime group 5 (processing before
the AND logic block)
The AND logic block is enabled by assigning to runtime group 5 (time
slice of 128 ms)
Run sequence of the AND logic block within runtime group 5 (processing
after the time block)
Setting the delay time of the time block: 5 seconds
Connect the status of DI 0 to the input of the time block
r0722.0 = Parameter that displays the status of digital input 0.
Interconnecting the time block to the 1st input of the AND
Interconnecting the status of DI 1 to the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
Interconnecting the AND output to the control command ON/OFF1
p0840
DI 0
r0722.0
Index [0]
Interconnect the BICO block DI 0 and ON/OFF1 command
p0840[0] = 0
DI 0
r0722.0
Disconnect the default interconnection: p0840[0] = 0
ON/
OFF1
p0840
ON/
Index [0]
OFF1
1.6 Extended scope for adaptation
Introduction
23