6.3.2

Communication parameters

Table 6- 4
Parameter
p0700 = 6
p1000 = 6
p0922
Using parameter p0922, you automatically interconnect the corresponding signals of the
inverter to the telegram.
This BICO interconnection can only be changed, if you set p0922 to 999. In this case, select
your required telegram using p2079 and then adapt the BICO interconnection of the signals.
Table 6- 5
Parameter
p2079
For further information, please refer to the Parameter Manual.
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
The most important parameters
Description
Command source selection
Selecting the fieldbus as command source
Speed setpoint selection
Selecting the fieldbus as setpoint source
PROFIdrive telegram selection (factory setting for CU with PROFIBUS interface: 1)
Set the send and receive telegram, see
1:
Standard telegram 1, PZD-2/2
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, BW-PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, BW-PKW-4/4
999:
Free telegram configuring with BICO
Advanced settings
Description
PROFIdrive PZD telegram selection extended
Contrary to p0922, using p2079, a telegram can be set and subsequently extended.
For p0922 < 999, the following applies: p2079 has the same value and is locked. All of
the interconnections and extensions contained in the telegram are locked.
For p0922 = 999, the following applies: p2079 can be freely set. If p2079 is also set to
999, then all interconnections can be set.
For p0922 = 999 and p2079 < 999, the following applies: The interconnections
contained in the telegram are locked. However, the telegram can be extended.
Connection to a fieldbus
6.3 Communication via PROFIBUS
You set the command and setpoint source
during the basic commissioning, see
Commissioning (Page 55)