Parameter Description
P1201
P1202
P1203
204
Advanced settings
Flying restart enable signal source (factory setting: 1)
Defines a control command, e.g. a digital input, through which the flying restart function
is enabled.
Flying restart search current (factory setting 100 %)
Defines the search current with respect to the motor magnetizing current (r0331), which
flows in the motor while the flying restart function is being used.
Flying restart search speed factor (factory setting 100 %)
The value influences the speed with which the output frequency is changed during the
flying restart. A higher value results in a longer search time.
If the inverter does not find the motor, reduce the search speed (increase p1203).