Analog Inputs - Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

5.4

Analog inputs

Depending on the design of the Control Unit, the inverter features one or two analog inputs.
Table 5- 7
Terminal Analog input
3
4
10
11
This section shows how to set the analog input as either a voltage or current input. BICO
technology can be used to set further interconnection of the analog input, e.g. as a speed
setpoint or setpoint for the technology controller. For more information, see the parameter list
and in the function block diagrams 9566 ff of the List Manual.
If you have selected "Control via terminals" in the basic commissioning, then analog input 0
is already interconnected with the speed setpoint.
Analog input as voltage or current input
Using parameter p0756, you define whether the analog input is used as voltage input (10 V)
or as current input (20 mA). p0756[0] is valid for analog input 0 and p0756[1] for analog
input 1.
The following options are available:
AI 0
AI 1
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Pre-assignment of the analog inputs
Parameter
AI 0+
AI 0
p0756[0]
AI 0-
AI 1+
AI 1
p0756[1]
AI 1-
Unipolar voltage input
Unipolar voltage input monitored
Unipolar current input
Unipolar current input monitored
Bipolar voltage input
No sensor connected
Unipolar voltage input
Unipolar voltage input monitored
Unipolar current input
Unipolar current input monitored
Bipolar voltage input
No sensor connected
Factory setting
4
Bipolar voltage input -10 V ... +10 V
4
Bipolar voltage input -10 V ... +10 V
Not available with Control Units CU240B-2 and
CU240B-2 DP
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
-10 V ... +10 V
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
-10 V ... +10 V
Configuring the terminal block
5.4 Analog inputs
p0756[0] =
p0756[1] =
0
1
2
3
4
8
0
1
2
3
4
8
97

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120 cu240e-2Sinamics g120 cu240b-2 dpSinamics g120 cu240e-2 dpSinamics g120 cu240e-2 fSinamics g120 cu240e-2 dp-f

Table of Contents