Index 80N0 Ai Settings (For 0 ≤ N ≤ F) - ICP DAS USA ECAT-2011H User Manual

Ethercat slave i/o modules
Table of Contents

Advertisement

ECAT-2011H EtherCAT Slave I/O module
Index 80n0 AI Settings
Index
Name
80n0:00
AI Settings
80n0:01
Enalbe user scale
80n0:02
Presentation
80n0:05
Enable Channel
80n0:06
Enalbe filter
80n0:07
Enable limit 1
80n0:08
Enalbe limit 2
80n0:09
Analog input type
80n0:0A
Enalbe user calibration Enabling of the user calibration
Enalbe vendor
80n0:0B
calibration
80n0:0E
Swap limit bits
Copyright © 2018 ICP DAS CO., Ltd. All Rights Reserved.
(for 0 ≤ n ≤ F)
Meaning
Maximum subindex
User scale is active
Change the method of representation
of the measured value.
0: Signed presentation
( Refer to
below )
Table 4-2-1
1: Unsigned presentation
( Refer to
Table 4-2-2
below )
2: Absolute value with MSB as sign
Signed amount representation
( Refer to
below )
Table 4-2-3
Enable Channel
Enable filter, which makes
PLC-cycle-synchronous
data exchange unnecessary
Limit 1 enable
Limit 2 enable
0: Differential input
1: Single-ended input
Enabling of the vendor calibration
Swap limit bits
FALSE:
0: not active
1: value < limit value
2: value > limit value
3: value is equal to the limit value
TRUE:
0: not active
1: value < limit value
2: value > limit value
3: value is equal to the limit value
Data type
Flags
Default
UINT8
RW
0x1A(26dec)
BOOLEAN
RW
FALSE(0dec)
Bit3
RW
Signed(0dec)
BOOLEAN
RW
TRUE(1dec)
BOOLEAN
RW
FALSE(0dec)
BOOLEAN
RW
FALSE(0dec)
BOOLEAN
RW
FALSE(0dec)
NIT32
RW
Differential (0dec)
BOOLEAN
RO
FALSE(0dec)
BOOLEAN
RW
TRUE(1dec)
BOOLEAN
RW
FALSE(0dec)
- 31 -