Output dry port (X2 and X1)

X2 terminals can hold Cable from 0.2mm2 – 1.5mm2
X2 are potential free contacts and are rated: Max 250Vac/8A; 30Vdc/8A; 220Vdc/0.12A
Block
Terminal
Contact
X2 / 18
C
X2 / 17
NC
NO
X2 / 16
X2 / 15
C
X2 / 14
NC
NO
X2 / 13
X2 / 12
C
X2 / 11
NC
NO
X2 / 10
X2
X2 / 9
C
X2 / 8
NC
NO
X2 / 7
X2 / 6
C
X2 / 5
NC
NO
X2 / 4
X2 / 3
C
X2 / 2
NC
NO
X2 / 1
X1 / 2
X1
X1 / 1
Signal
On Display
-
-
-
COMMON_ALARM
ALARM
LOAD_ON_MAINS
Message
BATT_LOW
ALARM
LOAD_ON_INV
Message
MAINS_OK
ALARM
-
EXT_MAN_BYP
-
Function
Common
Relays AUX
(Function on request, to be defined)
Common
No Alarm Condition
Common Alarm (System)
Common
No Load on Bypass
Load On Bypass (Mains)
Common
Battery Ok
Battery Low
Common
No Load on Inverter
Load on Inverter
Common
Mains Failure
Mains Present
Interlock Function
Max. 30Vdc/2A; 60Vdc/0.7A
(Ext Manual Bypass) / 2AT