10.8.4 CUSTOMER INTERFACES (Terminals X1....X4)
10.8.5 CUSTOMER INPUTS DRY PORT s:
Connection of Remote Shut down facilities, Generator Operation, Customers specials
(see UM Section 9 / OPTIONS)

10.8.6 CUSTOMER OUTPUTS DRY PORTs : Terminal blocks X2, X3, X4

Provision of signals for the automatic and orderly shutdown of servers, AS400 or Automation building systems
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires : 0.5 mm2
Block
Terminal
Contact
X1 / 1
X1 / 2
X1 / 3
X1 / 4
X1 / 5
X1
X1 / 6
X1 / 7
X1 / 8
X1 / 9
X1 / 10
X2 / 1
NO
X2 / 2
NC
X2 / 3
C
X2 / 4
NO
X2 / 5
NC
X2
X2 / 6
C
X2 / 7
NO
NC
X2 / 8
X2 / 9
C
X2 / 10
NO
X3 / 1
NC
X3 / 2
C
X3 / 3
NO
X3 / 4
NC
X3 / 5
C
X3
X3 / 6
NO
X3 / 7
NC
X3 / 8
C
X3 / 9
NO
X3 / 10
NC
X4 / 1
C
X4 / 2
NO
X4 / 3
NC
X4 / 4
C
X4 / 5
NO
X4
X4 / 6
NC
C
X4 / 7
X4 / 8
NO
X4 / 9
NC
X4 / 10
C
Phoenix Spring Terminals (X1...X4) Connection
Terminal block X1
Signal
On Display
IN
+ 3.3 Vdc
GND
GND
IN
+ 3.3 Vdc
GND
GND
IN
+ 3.3 Vdc
GND
GND
IN
+ 3.3 Vdc
GND
GND
IN
+ 3.3 Vdc
GND
GND
MAINS_OK
ALARM
LOAD_ON_INV
Message
BATT_LOW
ALARM
LOAD_ON_MAINS
Message
COMMON_ALARM
ALARM
MODUL_ALARM1
ALARM
MODUL_ALARM2
ALARM
MODUL_ALARM3
ALARM
MODUL_ALARM4
ALARM
MODUL_ALARM5
ALARM
04-3008_S10_ABB_TDSCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
Function
Remote Shut down
(Do not remove the factory mounted bridge until external Remote Shut down is connected)
Generator Operation
(NC = Generator ON)
Customer IN 1
(Function on request, to be defined)
Customer IN 2
(Function on request, to be defined)
Temperature Battery
(If connected , the battery charger current if depending of the battery temp.)
Mains Present
Mains Failure
Common
Load on Inverter
(Load on Mains bypass)
Common
Battery Low
Battery OK
Common
Load on bypass (Mains)
(Load on Inverter)
Common
Common Alarm (System)
NO Alarm Condition
Common
Module 1 Alarm
NO Alarm Condition
Common
Module 2 Alarm
NO Alarm Condition
Common
Module 3 Alarm
NO Alarm Condition
Common
Module 4 Alarm
NO Alarm Condition
Common
Module 5 Alarm
NO Alarm Condition
Common
Section-10
Page 12/19 ABB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents