Commissioning / Operation / Maintenance
5.5.3.1.3
Redundant AddFEM (Operating Mode 2)
At Operating Mode 2 the two AddFEMs which exist physically are docked "vir-
tually" to the PROFIBUS DP line of the SIMATIC S7–400.

Figure 5-20 AddFEM redundant

The two AddFEMs have to be configured with different PROFIBUS DP addresses.
Interface A is assigned at each module. The configuration of the two modules has
to be absolutely identical, with the exception of the PROFIBUS DP address.
Note
Operating Mode 2 "
displayed modules.
5-42
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
AS not red. AddFEM red." has to be set individually at each of the
AddFEM
AddFEM
C79000–G8076–C900–03