Start–up Characteristics
During an initial start–up or restart the logical address of the inputs and outputs
and the diagnostic address are formed from the geographic AddFEM address.
The range limits (AIx_HRG and AIx_LRG) are converted into factors and offsets in
order to calculate the current input values. In case of incorrect error configuration,
for example Upper limit <= Lower limit the input value is set to "zero.
During start–up a factor for calculating the speed (rpm) is calculated for each coun-
ter value. The number of pulses per revolution (number of teeth) has to be configu-
red at the Cox_NUM input parameters.
Time Response
Does not exist.
Message Characteristics
The block does not have message characteristics.
Operator Control and Monitoring
The block does not have a faceplate.
Parameters
AddFEM
C79000–G8076–C900–03