6.5.1. Optical fibers

NOTICE
Handle optical fibers with care. A damaged or incorrectly installed optical
fiber cable can degrade data transmission and cause equipment failure.
Only use the designated encoder cable conduit that passes through
the drive to the EXU.
The conduit extends 10 – 20 mm from the entry plate of the drive.
Cover the cable end with a cap BEFORE you pull the cable through
the conduit.
DO NOT exceed the maximum tensile load of 1.0 N and the minimum
bend radius of 25 mm.
When you tighten the cable ties DO NOT deform the optical fibers and
DO NOT use a cable tie gun.
Hold the connector when you connect or disconnect an optical fiber.
Optical fibers for internal arc protection
NOTICE
Optical fiber cables are only available in standard lengths.
DO NOT cut or extend the cables
Wind up excess cable in coils with a minimum diameter of 100 mm.
Each unit with power cable entries and terminals is monitored for arc faults by the
Arc Guard System™ with up to 4 detectors. See the project-specific "Converter
hardware diagram" on page 392 for the exact number of detectors in each cubicle.
The Arc Guard unit and the HMI panel are in the COU (Fig. 3-15) and the detectors
are pre-installed in the relevant cabinets. The optical fibers, which are coiled up
beside the detectors, must be routed from the detectors to the Arc Guard unit in
the COU.
PRODUCT
ACS5000W
Risk of equipment failure!
Risk of cable damage.
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
ELECTRICAL INSTALLATION
REV.
LANG.
PAGE
F
en
92/178