6.7.1.2. Preparing cables for cable entries with cable glands
Prepare cables with an outer cable screen or shield for EMC bonding with the metal
enclosure of the cabinet as illustrated.
1
2
3
Figure 6-14 Preparing power cables for cable glands
1) Cable gland
2) Plate
3) Heat-shrinkable termination
4) Outer cable sheath
PRODUCT
ACS5000W
4
5
6
DOCUMENT KIND
User manual
7
5) Conductor insulation removed to expose
cable shield
6) Cable screen extension to be connected to
PE ground busbar
7) Sheath seal
DOCUMENT ID.
3BHS799208 E01
ELECTRICAL INSTALLATION
REV.
LANG.
PAGE
F
en
100/178