Connecting Cables In Cou; Figure 6-24 Shield Grounding Clamp; Figure 6-25 Cou Customer Interface Section - ABB ACS5000 User Manual

Water-cooled system drives
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

6.8.2.2. Connecting cables in COU

Shielded cables
If you use twisted pair cables, leave the unshielded cable ends twisted until
they reach the terminals.
Leave unshielded conductor ends as short as possible.
Use a shield grounding clamp (Fig. 6-24) to fasten the overall shield and the
individual shields to the ground busbar (Fig. 6-24: 8).

Figure 6-24 Shield grounding clamp

1
2
3

Figure 6-25 COU customer interface section

1) Arc Guard™
2) Remote condition monitoring NETA-21 and
fieldbus interface
3) Customer terminals
4) S800 I/O process system
(customer- specific configuration)
PRODUCT
ACS5000W
DOCUMENT KIND
User manual
4
5
5) Grey encoder (optional)
6) NTAC-02 pulse encoder (optional)
7) Customer terminals
DOCUMENT ID.
3BHS799208 E01
ELECTRICAL INSTALLATION
6
7
REV.
LANG.
PAGE
F
en
111/178