of parameters that are successfully changed and failed to be changed are displayed beside
Submit.
Step 4 Select the All Configured Data tab page to view the configured device performance
parameters.
----End

6.2 Setting ECC800-Pro Cascading

If multiple smart modules (≤ 3) are installed in the same room and the customer has not
deployed the NetEco, multiple ECC800-Pros can be cascaded for management. To set the
cascading function, follow the procedure in this section.
Prerequisites
Cascaded ECC800-Pros communicate with each other properly.
Context
A maximum of three ECC800-Pros can be cascaded. After the IP addresses of other smart
module ECC800-Pros in the room are added to an ECC800-Pro, their active alarms and PUE
data can be displayed and viewed.
You can click links on the cascading management page of the master ECC800-Pro to display
the login pages of the other ECC800-Pros. Then, you can log in to view the details.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Smart Module Cascading.
Step 3 Click Add. In the displayed New Smart Module Cascading dialog box, enter the IP
addresses of the ECC800-Pros to be cascaded.
Step 4 Click Confirm.
Step 5 Choose Home > Multi-Module Monitoring. The information about the cascaded
ECC800-Pros is displayed.