Cooling Capacity Management; Optional) Setting Cooling Management Parameters - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Item
8
9
----End

6.12 Cooling Capacity Management

6.12.1 (Optional) Setting Cooling Management Parameters

Working Principle of the iCooling Function
The smart cooling product models that support iCooling linkage are air cooled smart cooling
products (NetCol5000-A025, NetCol5000-A042, and NetCol5000-A050). The function of
iCooling linkage is to enable smart cooling products to quickly respond to load changes and
implement on-demand cooling. Multiple smart cooling products in a smart module and the
indoor and outdoor units of a smart cooling product can be regulated to achieve optimal
energy efficiency without hotspots.
Prerequisites for the iCooling Function
Before setting the iCooling function, the following requirements must be met:
Issue 06 (2020-04-22)
Specifications
SPD
Main switch
iCooling disabled
For the cold aisle containment in the smart module, all IT cabinets use the cooling
capacity in the cold aisle and the temperatures inside the cold aisle are unevenly
distributed due to the uneven air flow.
The cooling requirements of the IT cabinets can be met and partial hot spots can be
avoided only if the cooling capacity provided by the smart cooling product matches
the heat load of the corresponding IT cabinets.
iCooling enabled
The cold aisle is divided into multiple areas according to the smart cooling product
positions. The cooling capacity from any smart cooling product in the areas can
meet the temperature requirements of the IT cabinets because the temperature
unevenness is relatively low.
The smart cooling products in each area quickly respond to load changes in the
areas and are regulated to achieve optimal energy efficiency.
Determine the installation position for the cabinet temperature sensor in strict accordance
with the requirements in the installation guide.
After installing the cabinet equipment, use filler panels to seal the vacant U space.
The smart module plan view has been created. The positions of devices in the smart
module plan view must be the same as their actual locations.
All smart cooling products in the smart module need to be networked for teamwork. For
details about how to configure teamwork networking, see the smart cooling product user
manual of the corresponding model. One smart module has only one group. In this group,
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
191

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800-pro

Table of Contents