How To Set And Add An Independent Deployment Ai_Di Unit - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Step 4 Set IP device num to 5. The value range is 0 to 100.
Step 5 Click Submit. The IP Device 1-5 tab page is displayed.
Step 6 On the IP Device 1-5 tab page, set Enable online detection IP device 1 to Enable.
Step 7 Click Submit.
Step 8 Specify IP device 1 address.
Step 9 Click Submit.
Step 10 (Optional) If you need to change the name of an IP device, perform the following steps:
1.
2.
3.
----End

8.1.6.18 How to Set and Add an Independent Deployment AI_DI Unit?

Prerequisites
One end of the straight-through cable has been connected to the COM_IN port on the
independent deployment AI_DI unit, and the other end has been connected to the COM port
on the ECC800-Pro collector or ETH converter.
Procedure
Step 1 Set monitoring parameters for the independent deployment AI_DI unit.
Set the address of the independent deployment AI_DI unit to 1 or 2 by setting its DIP switch.
The DIP switch consists of toggle switches 1–4 (from left to right). Toggle switches 1–3
specify the address of the independent deployment AI_DI unit. Toggle switch 4 specifies the
address of the RS485 build-out resistor. 1 indicates ON, and 0 indicates OFF.
Table 8-15 Setting a device address
Address
Issue 06 (2020-04-22)
Online detection timeout interval is 30 by default, which means that the ECC800-Pro determines that
the communication with the device is interrupted if the device has no response within 30 seconds.
Set IP device 1 address to the IP address of IP device 1. For example, set IP device 1 address to
192.168.2.137.
Add other IP devices in the same way.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device type to ECC800, set Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of IP device 1 to XXX and click
Submit.
The device address for the independent deployment AI_DI unit can only be set to 1 or 2.
Toggle Switch 1
Copyright © Huawei Technologies Co., Ltd.
Toggle Switch 2
8 FAQ
Toggle Switch 3
248

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800-pro

Table of Contents